The Fan Tray Unit (FTU) is used in the TJ1600 Type-2SR chassis to cool the equipment. There are two fans present in the fan tray unit.

Front panel

Following figure shows the front panel diagram of FTU card:

TJ1600-2 FTU - Front panel

Power specifications

Power specifications - FTU

Specification

Range

Input Voltage

-48V DC

Power consumption

92W

LED Indication

Sts LED- FTU

Indication

Description

Sts LED Green

Indicates FTU is active and functional

Sts LED OFF

Indicates FTU is not powered on.

Sts LED RED

Indicates card failure.

Functional description

The following are the functional features of FTU:

Important considerations for FTU:

  1. In case of single fan failure, the system works up to 40°C temperature. An Alarm is raised if any of the fans fails (the Fan tray is provided with two fans). The fan needs to be replaced, if an alarm exists on the FTU. If the alarm exists on the FTU and if the room temperature is below 40°C, the system works unless the second fan fails.
  2. Ensure that the fan tray unit is not removed before the replacement unit is available. Also ensure that the FTU replacement procedure is completed within 30 seconds time.
  3. Air filter is to be examined regularly at least once in 3 months. If appears dirty and clogged then to be cleaned or replaced. Cleaning to be done with vacuum cleaner.

See also

Fan Tray Units

HCPFTU01

HCPFTU02