The Fan Tray Unit (FTU) is used in the TJ1600 Type-2SR chassis to cool the equipment. There are two fans present in the fan tray unit.
Front panel
Following figure shows the front panel diagram of FTU card:
Power specifications
Power specifications - FTU
Specification
Range
Input Voltage
-48V DC
Power consumption
92W
LED Indication
Sts LED- FTU
Indication
Description
Sts LED Green
Indicates FTU is active and functional
Sts LED OFF
Indicates FTU is not powered on.
Sts LED RED
Indicates card failure.
Functional description
The following are the functional features of FTU:
Two fans.
Fuse on each fan power supply to isolate any failed fan from other fan.
Fan speed monitoring and control through software, based on the temperature sensed.
Temperature monitoring on the airflow path.
Field replaceable.
Separate Air filter as a Field replaceable unit.
Air filter is to be examined regularly once in 3 months. If appears dirty and clogged then to be cleaned or replaced. Cleaning to be done with vacuum cleaner.
The fan in the FTU is designed to have redundancy and the two fans do not fail simultaneously at any point of time.
Important considerations for FTU:
In case of single fan failure, the system works up to 40°C temperature. An Alarm is raised if any of the fans fails (the Fan tray is provided with two fans). The fan needs to be replaced, if an alarm exists on the FTU. If the alarm exists on the FTU and if the room temperature is below 40°C, the system works unless the second fan fails.
Ensure that the fan tray unit is not removed before the replacement unit is available. Also ensure that the FTU replacement procedure is completed within 30 seconds time.
Air filter is to be examined regularly at least once in 3 months. If appears dirty and clogged then to be cleaned or replaced. Cleaning to be done with vacuum cleaner.