The Fan Tray Unit (HCPFTU02) is used in the TJ1600 Type-6SR chassis to cool the equipment. There are four fans present in the fan tray unit.
Front Panel
The following figure shows the front panel view of HCPFTU02:
Power Specifications
Power Specifications - HCPFTU02
Specification
Range
Input Voltage
-48V DC
Power consumption
192 watt
LED Indication
Sts LED- HCPFTU02
Indication
Description
Sts LED Green
Indicates FTU02 is active and functional
Sts LED OFF
Indicates FTU02 is not powered on.
Sts LED RED
Indicates card failure.
Functional Description
The functional features of HCPFTU02 are as follows:
Four fans.
Fuse on each fan power supply to isolate any failed fan from other fans.
Fan speed monitoring and control through software, based on the temperature sensed.
Temperature monitoring on the airflow path.
Field replaceable.
Separate Air filter as a Field replaceable unit.
The fan in the FTU is designed to have redundancy and the two fans do not fail simultaneously at any point of time.
Important considerations for FTU:
In case of single fan failure, the system works up to 40°C temperature. An Alarm is raised if any of the fans fails (the Fan tray is provided with six fans). The fan needs to be replaced, if an alarm exists on the FTU. If the alarm exists on the FTU and if the room temperature is below 40°C, the system works unless the second fan fails.
Ensure that the fan tray unit is not removed before the replacement unit is available. Also ensure that the FTU replacement procedure be completed in 30 seconds time.
Air filter is to be examined regularly at least once in 3 months. If appears dirty and clogged then to be cleaned or replaced. Cleaning to be done with vacuum cleaner.