The Power Filter Unit (PFU) supported in TJ1600-2 chassis supports load sharing on redundancy basis i.e. if one PSU fails, other will be the active load driver and provide a stable DC power to other cards in the system. The unit provides a filtered input voltage of -40V to -57.6V to the chassis and the cards on the chassis.
An EMI filter is used to restrict conducted emissions. The filters have transient voltage suppressors to prevent voltage surges affecting the system.
Functional features of the PFU:
Front panel
The front panel of this unit provides a power connector and a local safety ground connection.
Visual indicator details
LED |
Color |
Remarks |
|
---|---|---|---|
Power
|
This is with redundant power supply in the system. |
||
Red |
When the card is jacked in without input feed. Output voltage out of range. Red will blink if card goes for over current protection. |
||
Green |
Card is working fine. Green will blink when the card goes down because of input voltage protection. |
||
Red and Green |
Red and Green will blink alternatively if card goes for over temperature protection. |
||
Power
|
If there is no redundant power supply in the system. |
||
Red |
Output voltage out of range. Red will blink if card goes for over current protection. |
||
Green |
Card is working fine. Green will blink when the card goes down because of input voltage protection. |
||
Red and Green |
Red and Green will blink alternatively if card goes for over temperature protection. |
||
Blank |
If input is not present. |
Operational specifications
Specification |
Range |
---|---|
Input Voltage Range |
-40V to -57.6V DC |
Reverse Polarity Protection |
Continuous |
Input Current |
11A continuous at nominal voltage, 12.5A maximum at -40V during the operation. |
Maximum operating Ambient Temperature |
-5°C to 55°C |
Output Voltage |
-40V to -57.6V DC |
Output Current |
8.68A (min) to 12.5A (min) from 40V to 57.6V, maximum power of 500W at any input voltage. |
Output Power |
|
Ripple |
|
Dynamic response |
|
Efficiency |
>99% Load when input is -48V DC |
Fuse |
20A Telecom fuse |
Under Voltage Protection |
|
Over Voltage Protection |
|
Hold-up Time (Interruption) |
0.5ms at 53.5V and above. |
Power Interface |
|
Protections |
|