Fan Tray Unit

The Fan Tray Unit - HCPFTU02 is used in the TJ1600-6 node to cool the equipment. There are four fans present in the fan tray unit.

The functional features of HCPFTU02 are as follows:

Important considerations for FTU:

  1. In case of single fan failure, the system works up to 40°C temperature. An Alarm is raised if any of the fans fails (the Fan tray is provided with six fans). The fan needs to be replaced, if an alarm exists on the FTU. If the alarm exists on the FTU and if the room temperature is below 40°C, the system works unless the second fan fails.
  2. Ensure that the fan tray unit is not removed before the replacement unit is available. Also ensure that the FTU replacement procedure be completed in 30 seconds time.
  3. Air filter is to be examined regularly at least once in 3 months. If appears dirty and clogged then to be cleaned or replaced. Cleaning to be done with vacuum cleaner.

Front panel

The following figure shows the front panel view of HCPFTU02.

TJ1600-6 HCPFTU02 - Front panel

Power specifications

TJ1600-6 HCPFTU02 - Power Specifications

Specification

Range

Input Voltage

-48V DC

Power consumption

192 watt

Visual LED indication

Status LED indicates the status of the power supply to the FTU ET.

LED

Color

Description

Sts

Green

Indicates FTU02 is active and functional.

Off

Indicates FTU02 is not powered on.

Red

Indicates card failure.

See also

TJ1600-6

System specification

Power Filter Unit

Slot allotment and bandwidth allocation

Cards overview

Interfaces