The Fan Tray Unit - HCPFTU02 is used in the TJ1600-6 node to cool the equipment. There are four fans present in the fan tray unit.
The functional features of HCPFTU02 are as follows:
Four fans.
Fuse on each fan power supply to isolate any failed fan from other fans.
Fan speed monitoring and control through software, based on the temperature sensed.
Temperature monitoring on the airflow path.
Field replaceable.
Separate Air filter as a Field replaceable unit.
The fan in the FTU is designed to have redundancy and the two fans do not fail simultaneously at any point of time.
Important considerations for FTU:
In case of single fan failure, the system works up to 40°C temperature. An Alarm is raised if any of the fans fails (the Fan tray is provided with six fans). The fan needs to be replaced, if an alarm exists on the FTU. If the alarm exists on the FTU and if the room temperature is below 40°C, the system works unless the second fan fails.
Ensure that the fan tray unit is not removed before the replacement unit is available. Also ensure that the FTU replacement procedure be completed in 30 seconds time.
Air filter is to be examined regularly at least once in 3 months. If appears dirty and clogged then to be cleaned or replaced. Cleaning to be done with vacuum cleaner.
Front panel
The following figure shows the front panel view of HCPFTU02.
Power specifications
TJ1600-6 HCPFTU02 - Power Specifications
Specification
Range
Input Voltage
-48V DC
Power consumption
192 watt
Visual LED indication
Status LED indicates the status of the power supply to the FTU ET.